SPG-12 Outdoor SF6 Load Break Switch (12kV)
The SPG-12 is a 12kV outdoor SF6 load break switch for 10kV distribution systems. Uses SF6 pressure-assisted arc blowing in a 304 stainless steel molded housing — low gas pressure means low heat, short extinguishing time, and long life. Features low gas pressure interlock (locks operation at 0.03-0.04 MPa with visual alarm), manual interlock for safe maintenance, and high-pressure explosion-proof relief (0.4-0.6 MPa with side venting, no solid particle ejection). Silicone rubber/epoxy resin insulation with APG integral vacuum casting — 20+ years outdoor proven. Every unit X-ray inspected. Triangle spring mechanism sealed in SF6 housing — rust-free, maintenance-free. Capable of zero-gauge-pressure rated current switching. 5,000 mechanical operations life.
Caracteristiques Principales
- 12kV rated voltage — for 10kV distribution systems
- SF6 pressure-assisted arc blowing — low heat, fast extinction, long life
- 304 stainless steel molded housing — annual leak rate far exceeds national standard
- Zero-gauge-pressure rated current switching capability
- Low gas pressure interlock: 0.03-0.04 MPa with visual alarm
- Manual interlock for safe maintenance operations
- High pressure explosion-proof relief: 0.4-0.6 MPa, side venting, no debris
- Silicone rubber / epoxy resin insulation (APG vacuum cast)
- Triangle spring mechanism sealed in SF6 — rust-free, maintenance-free
- Every unit X-ray inspected for quality
- Mechanical life: 5,000 operations
- Compatible with FTU for distribution automation (FA/DA)
Specifications Techniques
| Rated Voltage | 12 kV |
| Rated Frequency | 50/60 Hz |
| Rated Current | 630 A |
| Rated Breaking Load Current | 630 A |
| Rated Closed Breaking Current | 630 A |
| Rated Short-Circuit Making Current (peak) | 50 kA |
| Rated Short-Time Withstand Current | 20 kA / 4s |
| Rated Cable-Charging Breaking Current | 10 A |
| Rated Earth Fault Breaking Current | 48 A |
| Lightning Impulse Withstand (phase-phase/earth) | 75 kV |
| Lightning Impulse Withstand (across isolating distance) | 85 kV |
| Power Frequency Withstand 1min (phase-phase/earth) | 42 kV |
| Power Frequency Withstand 1min (across isolating distance) | 48 kV |
| Rain Test Withstand Voltage | 34 kV |
| Rated Working Pressure | 0.07 MPa |
| Low Pressure Interlock | 0.03-0.04 MPa |
| High Pressure Explosion Relief | 0.4-0.6 MPa |
| Annual Leak Rate | ≤0.5% |
| SF6 Water Content | ≤150 PPM |
| Circuit Resistance (per phase) | ≤150 μΩ |
| Contact Distance | 41±3 mm |
| Contact Overtravel | 22±2 mm |
| Opening Speed | 1.9±0.2 m/s |
| Closing Speed | 1.9±0.2 m/s |
| Contact Closing Bounce Time | ≤3 ms |
| Phase-to-Phase Distance | 250±3 mm |
| Three-Phase Synchronization | ≤3 ms |
| Closing Time | <10 s |
| Opening Time | <10 s |
| Energy Storage Motor Power | 40 W |
| Mechanical Life | 5,000 operations |
| Operation Voltage | DC220V / DC24V / AC220V |
| Weight (Manual / Automatic) | 115 kg / 135 kg |
| Temperature Range | -25°C to +40°C |
Applications
Conformite aux Normes
Questions Frequentes
Quelle est la tension nominale du SPG-12 Outdoor SF6 Load Break Switch (12kV)?
Quel est le delai de livraison pour le SPG-12 Outdoor SF6 Load Break Switch (12kV)?
Le SPG-12 Outdoor SF6 Load Break Switch (12kV) peut-il etre personnalise pour des projets OEM?
A quelles normes le SPG-12 Outdoor SF6 Load Break Switch (12kV) est-il conforme?
Interesse par le SPG-12 Outdoor SF6 Load Break Switch (12kV)?
Obtenez des prix directs usine, des specifications techniques et des options de configuration personnalisee.