SPG-24 Outdoor SF6 Load Break Switch (24kV)
Sakelar Beban SF6

SPG-24 Outdoor SF6 Load Break Switch (24kV)

The SPG-24 is a 24kV outdoor SF6 load break switch for 20kV distribution systems. Enhanced insulation levels with 125/145kV lightning impulse withstand. Same proven SF6 pressure-assisted arc blowing technology in 304 stainless steel housing. Available in 630A and 1250A rated current variants. Features all safety interlocks (low pressure, manual, explosion-proof relief). Silicone rubber/epoxy resin insulation with APG vacuum casting. Every unit X-ray inspected. 5,000 mechanical operations life.

Fitur Utama

  • 24kV rated voltage — for 20kV distribution systems
  • Enhanced insulation: 125/145kV lightning impulse withstand
  • Available in 630A and 1250A rated current variants
  • SF6 pressure-assisted arc blowing — proven reliability
  • 304 stainless steel molded housing
  • Low gas pressure interlock: 0.03-0.04 MPa with visual alarm
  • Manual interlock + high pressure explosion-proof relief
  • Silicone rubber / epoxy resin insulation (APG vacuum cast)
  • Triangle spring mechanism sealed in SF6 — maintenance-free
  • Every unit X-ray inspected
  • Mechanical life: 5,000 operations
  • Compatible with FTU for 20kV distribution automation

Spesifikasi Teknis

Rated Voltage24 kV
Rated Frequency50/60 Hz
Rated Current630 / 1250 A
Rated Breaking Load Current630 / 1250 A
Rated Closed Breaking Current630 / 1250 A
Rated Short-Circuit Making Current (peak)50 / 63 kA
Rated Short-Time Withstand Current20kA/4s, 25kA/4s
Rated Cable-Charging Breaking Current25 A
Rated Earth Fault Breaking Current48 A
Lightning Impulse Withstand (phase-phase/earth)125 kV
Lightning Impulse Withstand (across isolating distance)145 kV
Power Frequency Withstand 1min (phase-phase/earth)65 kV
Power Frequency Withstand 1min (across isolating distance)79 kV
Rain Test Withstand Voltage50 kV
Rated Working Pressure0.20 MPa
Low Pressure Interlock0.03-0.04 MPa
High Pressure Explosion Relief0.4-0.6 MPa
Annual Leak Rate≤0.5%
SF6 Water Content≤150 PPM
Circuit Resistance (per phase)≤150 μΩ
Contact Distance41±3 mm
Contact Overtravel22±2 mm
Opening Speed1.9±0.2 m/s
Closing Speed1.9±0.2 m/s
Contact Closing Bounce Time≤3 ms
Phase-to-Phase Distance250±3 mm
Three-Phase Synchronization≤3 ms
Closing Time<10 s
Opening Time<10 s
Energy Storage Motor Power40 W
Mechanical Life5,000 operations
Operation VoltageDC220V / DC24V / AC220V
Weight (Manual / Automatic)115 kg / 135 kg
Temperature Range-25°C to +40°C

Aplikasi

Urban distribution network sectionalizing (20kV)Tie switch applications for 20kV systemsRural distribution system control switchingRing network fault detection, isolation, and alarmDistribution automation with FTU

Kepatuhan Standar

IEC 62271-103GB/T 10963
Balasan dalam 12 jamBersertifikat ISO / CE / CCCOEM Tersedia

Pertanyaan yang Sering Diajukan

Berapa tegangan nominal SPG-24 Outdoor SF6 Load Break Switch (24kV)?
SPG-24 Outdoor SF6 Load Break Switch (24kV) memiliki tegangan nominal 24 kV. Silakan lihat tabel spesifikasi teknis untuk peringkat listrik lengkap.
Berapa waktu pengiriman untuk SPG-24 Outdoor SF6 Load Break Switch (24kV)?
Waktu pengiriman standar untuk SPG-24 Outdoor SF6 Load Break Switch (24kV) sekitar 30 hari. Jumlah lebih besar mungkin memerlukan waktu produksi tambahan.
Bisakah SPG-24 Outdoor SF6 Load Break Switch (24kV) dikustomisasi untuk proyek OEM?
Ya, NAIJI Electric menawarkan manufaktur OEM dan kustom untuk SPG-24 Outdoor SF6 Load Break Switch (24kV).
Standar apa yang dipenuhi SPG-24 Outdoor SF6 Load Break Switch (24kV)?
SPG-24 Outdoor SF6 Load Break Switch (24kV) dirancang dan diuji sesuai IEC 62271-103, GB/T 10963. Semua produk menjalani pengujian ketat sebelum pengiriman.

Tertarik dengan SPG-24 Outdoor SF6 Load Break Switch (24kV)?

Dapatkan harga langsung pabrik, spesifikasi teknis dan opsi konfigurasi kustom.