SPG-12 Outdoor SF6 Load Break Switch (12kV)
Cau dao tai SF6

SPG-12 Outdoor SF6 Load Break Switch (12kV)

The SPG-12 is a 12kV outdoor SF6 load break switch for 10kV distribution systems. Uses SF6 pressure-assisted arc blowing in a 304 stainless steel molded housing — low gas pressure means low heat, short extinguishing time, and long life. Features low gas pressure interlock (locks operation at 0.03-0.04 MPa with visual alarm), manual interlock for safe maintenance, and high-pressure explosion-proof relief (0.4-0.6 MPa with side venting, no solid particle ejection). Silicone rubber/epoxy resin insulation with APG integral vacuum casting — 20+ years outdoor proven. Every unit X-ray inspected. Triangle spring mechanism sealed in SF6 housing — rust-free, maintenance-free. Capable of zero-gauge-pressure rated current switching. 5,000 mechanical operations life.

Dac diem chinh

  • 12kV rated voltage — for 10kV distribution systems
  • SF6 pressure-assisted arc blowing — low heat, fast extinction, long life
  • 304 stainless steel molded housing — annual leak rate far exceeds national standard
  • Zero-gauge-pressure rated current switching capability
  • Low gas pressure interlock: 0.03-0.04 MPa with visual alarm
  • Manual interlock for safe maintenance operations
  • High pressure explosion-proof relief: 0.4-0.6 MPa, side venting, no debris
  • Silicone rubber / epoxy resin insulation (APG vacuum cast)
  • Triangle spring mechanism sealed in SF6 — rust-free, maintenance-free
  • Every unit X-ray inspected for quality
  • Mechanical life: 5,000 operations
  • Compatible with FTU for distribution automation (FA/DA)

Thong so ky thuat

Rated Voltage12 kV
Rated Frequency50/60 Hz
Rated Current630 A
Rated Breaking Load Current630 A
Rated Closed Breaking Current630 A
Rated Short-Circuit Making Current (peak)50 kA
Rated Short-Time Withstand Current20 kA / 4s
Rated Cable-Charging Breaking Current10 A
Rated Earth Fault Breaking Current48 A
Lightning Impulse Withstand (phase-phase/earth)75 kV
Lightning Impulse Withstand (across isolating distance)85 kV
Power Frequency Withstand 1min (phase-phase/earth)42 kV
Power Frequency Withstand 1min (across isolating distance)48 kV
Rain Test Withstand Voltage34 kV
Rated Working Pressure0.07 MPa
Low Pressure Interlock0.03-0.04 MPa
High Pressure Explosion Relief0.4-0.6 MPa
Annual Leak Rate≤0.5%
SF6 Water Content≤150 PPM
Circuit Resistance (per phase)≤150 μΩ
Contact Distance41±3 mm
Contact Overtravel22±2 mm
Opening Speed1.9±0.2 m/s
Closing Speed1.9±0.2 m/s
Contact Closing Bounce Time≤3 ms
Phase-to-Phase Distance250±3 mm
Three-Phase Synchronization≤3 ms
Closing Time<10 s
Opening Time<10 s
Energy Storage Motor Power40 W
Mechanical Life5,000 operations
Operation VoltageDC220V / DC24V / AC220V
Weight (Manual / Automatic)115 kg / 135 kg
Temperature Range-25°C to +40°C

Ung dung

Urban distribution network sectionalizingTie switch applications for 10kV systemsRural distribution system control switchingRing network fault detection, isolation, and alarmDistribution automation with FTU

Tuan thu tieu chuan

IEC 62271-103GB/T 10963
Phan hoi trong 12hChung nhan ISO / CE / CCCCo san OEM

Cau hoi thuong gap

Dien ap dinh muc cua SPG-12 Outdoor SF6 Load Break Switch (12kV) la bao nhieu?
SPG-12 Outdoor SF6 Load Break Switch (12kV) co dien ap dinh muc 12 kV. Vui long xem bang thong so ky thuat de biet day du cac thong so dien.
Thoi gian giao hang cho SPG-12 Outdoor SF6 Load Break Switch (12kV) la bao lau?
Thoi gian giao hang tieu chuan cho SPG-12 Outdoor SF6 Load Break Switch (12kV) khoang 30 ngay. So luong lon hon co the can them thoi gian san xuat.
SPG-12 Outdoor SF6 Load Break Switch (12kV) co the tuy chinh cho du an OEM khong?
Co, NAIJI Electric cung cap san xuat OEM va tuy chinh cho SPG-12 Outdoor SF6 Load Break Switch (12kV).
SPG-12 Outdoor SF6 Load Break Switch (12kV) tuan thu nhung tieu chuan nao?
SPG-12 Outdoor SF6 Load Break Switch (12kV) duoc thiet ke va thu nghiem theo IEC 62271-103, GB/T 10963. Tat ca san pham trai qua kiem tra nghiem ngat truoc khi xuat hang.

Quan tam den SPG-12 Outdoor SF6 Load Break Switch (12kV)?

Nhan gia truc tiep tu nha may, thong so ky thuat va cac tuy chon cau hinh.