SPV-24 Outdoor Vacuum Circuit Breaker (24kV)
May cat chan khong

SPV-24 Outdoor Vacuum Circuit Breaker (24kV)

The SPV-24 is a 24kV oil-free, SF6-free, maintenance-free outdoor vacuum circuit breaker by NAIJI Electric. Extended voltage class with enhanced insulation levels (125/145kV lightning impulse withstand). Same proven longitudinal magnetic field rotating arc technology and solid epoxy resin insulation (APG vacuum casting) as the SPV-12. Every unit X-ray inspected. Weighs only 2/3 of comparable products. Ideal for 20kV distribution systems and higher voltage applications.

Dac diem chinh

  • 24kV rated voltage — higher insulation class, oil-free, SF6-free
  • Enhanced lightning impulse withstand: 125/145kV
  • Longitudinal magnetic field rotating arc — same proven technology as SPV-12
  • Solid epoxy resin insulation (APG vacuum cast) — 20+ years outdoor proven
  • Every unit 100% X-ray inspected
  • Mechanical life: 10,000 operations
  • Electrical life: 10,000+ operations at rated current
  • Only 2/3 weight of comparable products
  • Imported spring wire + bearing structure + zinc-nickel-cobalt alloy treatment
  • Compatible with FTU for 20kV distribution automation

Thong so ky thuat

Rated Voltage24 kV
Rated Current630 / 1250 A
Rated Frequency50 Hz
Rated Short-Circuit Breaking Current20 / 25 kA
Rated Peak Withstand Current50 / 63 kA
Rated Short-Circuit Making Current (peak)50 / 63 kA
Rated Short-Time Withstand Current20kA/4s, 25kA/4s
Rated Operating SequenceO—0.3s—CO—180s—CO
Short-Circuit Breaking Operations20 times
Lightning Impulse Withstand (phase-phase/earth)125 kV (peak)
Lightning Impulse Withstand (across isolating distance)145 kV (peak)
Power Frequency Withstand 1min Dry (phase/earth · across gap)65 / 79 kV
Power Frequency Withstand 1min Wet (phase/earth · across gap)50 / 64 kV
Secondary Circuit Withstand Voltage2000 V
Contact Distance12±1 mm
Contact Overtravel3.5±1 mm
Opening Speed1.4±0.2 m/s
Closing Speed0.7±0.2 m/s
Contact Closing Bounce Time≤2 ms
Phase-to-Phase Distance380±1.5 mm
Three-Phase Synchronization≤2 ms
Circuit Resistance (per phase)≤70 μΩ
Closing Time25~60 ms
Opening Time20~40 ms
Energy Storage Motor Power40 W
Mechanical Life10,000 operations
Electrical Life10,000+ operations
Insulation MediumSolid epoxy resin (APG vacuum cast)
Arc ExtinguishingLongitudinal magnetic field rotating arc
Temperature Range-25°C to +40°C
Weight2/3 of comparable products
MaintenanceMaintenance-free

Ung dung

20kV distribution network switchingHigh-voltage substationsIndustrial power supply systemsRenewable energy grid connectionsRing network sectionalizing (20kV systems)Distribution automation with FTU

Tuan thu tieu chuan

IEC 62271-100GB 1984
Phan hoi trong 12hChung nhan ISO / CE / CCCCo san OEM

Cau hoi thuong gap

Dien ap dinh muc cua SPV-24 Outdoor Vacuum Circuit Breaker (24kV) la bao nhieu?
SPV-24 Outdoor Vacuum Circuit Breaker (24kV) co dien ap dinh muc 24 kV. Vui long xem bang thong so ky thuat de biet day du cac thong so dien.
Thoi gian giao hang cho SPV-24 Outdoor Vacuum Circuit Breaker (24kV) la bao lau?
Thoi gian giao hang tieu chuan cho SPV-24 Outdoor Vacuum Circuit Breaker (24kV) khoang 30 ngay. So luong lon hon co the can them thoi gian san xuat.
SPV-24 Outdoor Vacuum Circuit Breaker (24kV) co the tuy chinh cho du an OEM khong?
Co, NAIJI Electric cung cap san xuat OEM va tuy chinh cho SPV-24 Outdoor Vacuum Circuit Breaker (24kV).
SPV-24 Outdoor Vacuum Circuit Breaker (24kV) tuan thu nhung tieu chuan nao?
SPV-24 Outdoor Vacuum Circuit Breaker (24kV) duoc thiet ke va thu nghiem theo IEC 62271-100, GB 1984. Tat ca san pham trai qua kiem tra nghiem ngat truoc khi xuat hang.

Quan tam den SPV-24 Outdoor Vacuum Circuit Breaker (24kV)?