SPV-12 Outdoor Vacuum Circuit Breaker (12kV)
Disjoncteurs a Vide

SPV-12 Outdoor Vacuum Circuit Breaker (12kV)

The SPV-12 is a 12kV oil-free, SF6-free, maintenance-free outdoor vacuum circuit breaker pioneered by NAIJI Electric. Features three-phase pillar-type structure with longitudinal magnetic field vacuum arc extinguishing technology and solid epoxy resin insulation (APG vacuum casting). The spiral groove contacts produce a rotating magnetic field, accelerating ionized particle diffusion and reducing arc energy. Special alloy shielding rapidly absorbs arc energy for low heat, short extinguishing time, and long service life. Imported outdoor-grade epoxy resin with integral vacuum casting — proven by 20+ years of outdoor operation with no surface carbonization. Every unit X-ray inspected. Weighs only 2/3 of comparable products.

Caracteristiques Principales

  • 12kV rated voltage — oil-free, SF6-free, maintenance-free
  • Longitudinal magnetic field rotating arc — spiral groove contacts for superior extinction
  • Solid epoxy resin insulation (APG vacuum cast) — UV, moisture, salt-fog resistant
  • Every unit 100% X-ray inspected
  • Mechanical life: 10,000 operations
  • Electrical life: 10,000+ operations at rated current
  • Only 2/3 weight of comparable products
  • Imported spring wire + bearing structure + zinc-nickel-cobalt alloy treatment
  • Aviation lubricant for extreme cold operation
  • Compatible with FTU for distribution automation (FA/DA)

Specifications Techniques

Rated Voltage12 kV
Rated Current630 / 1250 A
Rated Frequency50 Hz
Rated Short-Circuit Breaking Current20 / 25 kA
Rated Peak Withstand Current50 / 63 kA
Rated Short-Circuit Making Current (peak)50 / 63 kA
Rated Short-Time Withstand Current20kA/4s, 25kA/4s
Rated Operating SequenceO—0.3s—CO—180s—CO
Short-Circuit Breaking Operations30 times
Lightning Impulse Withstand (phase-phase/earth)75 kV (peak)
Lightning Impulse Withstand (across isolating distance)85 kV (peak)
Power Frequency Withstand 1min Dry (phase/earth · across gap)42 / 49 kV
Power Frequency Withstand 1min Wet (phase/earth · across gap)34 / 35 kV
Secondary Circuit Withstand Voltage2000 V
Contact Distance9±1 mm
Contact Overtravel2.5±0.5 mm
Opening Speed1.4±0.2 m/s
Closing Speed0.7±0.2 m/s
Contact Closing Bounce Time≤2 ms
Phase-to-Phase Distance340±1.5 mm
Three-Phase Synchronization≤2 ms
Circuit Resistance (per phase)≤70 μΩ
Closing Time25~60 ms
Opening Time20~40 ms
Energy Storage Motor Power40 W
Mechanical Life10,000 operations
Electrical Life10,000+ operations
Insulation MediumSolid epoxy resin (APG vacuum cast)
Arc ExtinguishingLongitudinal magnetic field rotating arc
Temperature Range-25°C to +40°C
MaintenanceMaintenance-free

Applications

Distribution network switching and protectionSubstations — load, overload and short-circuit current breakingIndustrial & mining enterprise distributionUrban and rural power gridsRing network sectionalizing and tie switchesFrequent operation applicationsDistribution automation with FTU (fault detection, isolation, alarm)

Conformite aux Normes

IEC 62271-100GB 1984
Reponse sous 12hCertifie ISO / CE / CCCOEM Disponible

Questions Frequentes

Quelle est la tension nominale du SPV-12 Outdoor Vacuum Circuit Breaker (12kV)?
Le SPV-12 Outdoor Vacuum Circuit Breaker (12kV) a une tension nominale de 12 kV. Consultez le tableau des specifications techniques pour les caracteristiques electriques completes.
Quel est le delai de livraison pour le SPV-12 Outdoor Vacuum Circuit Breaker (12kV)?
Le delai standard pour le SPV-12 Outdoor Vacuum Circuit Breaker (12kV) est d'environ 30 jours. Des quantites plus importantes ou des configurations personnalisees peuvent necessiter plus de temps.
Le SPV-12 Outdoor Vacuum Circuit Breaker (12kV) peut-il etre personnalise pour des projets OEM?
Oui, NAIJI Electric propose la fabrication OEM et sur mesure pour le SPV-12 Outdoor Vacuum Circuit Breaker (12kV).
A quelles normes le SPV-12 Outdoor Vacuum Circuit Breaker (12kV) est-il conforme?
Le SPV-12 Outdoor Vacuum Circuit Breaker (12kV) est concu et teste conformement aux normes IEC 62271-100, GB 1984. Tous les produits subissent des essais rigoureux avant expedition.

Interesse par le SPV-12 Outdoor Vacuum Circuit Breaker (12kV)?

Obtenez des prix directs usine, des specifications techniques et des options de configuration personnalisee.