SPG-24 Outdoor SF6 Load Break Switch (24kV)
SF6负荷开关

SPG-24 Outdoor SF6 Load Break Switch (24kV)

The SPG-24 is a 24kV outdoor SF6 load break switch for 20kV distribution systems. Enhanced insulation levels with 125/145kV lightning impulse withstand. Same proven SF6 pressure-assisted arc blowing technology in 304 stainless steel housing. Available in 630A and 1250A rated current variants. Features all safety interlocks (low pressure, manual, explosion-proof relief). Silicone rubber/epoxy resin insulation with APG vacuum casting. Every unit X-ray inspected. 5,000 mechanical operations life.

产品特点

  • 额定电压24kV——适用于20kV配电系统
  • 增强绝缘:雷电冲击耐受125/145kV
  • 可选630A和1250A两种额定电流规格
  • SF6压气式吹弧灭弧——可靠性高
  • 优质304不锈钢模压壳体
  • 低气压联锁:0.03-0.04 MPa,带视觉报警
  • 手动联锁+高压防爆泄压装置
  • 硅橡胶/环氧树脂绝缘(APG真空浇注)
  • 三角形弹簧机构密封于SF6壳体内——免维护
  • 每只成品逐一X光检查
  • 机械寿命:5,000次
  • 可配FTU实现20kV配电自动化

技术参数

Rated Voltage24 kV
Rated Frequency50/60 Hz
Rated Current630 / 1250 A
Rated Breaking Load Current630 / 1250 A
Rated Closed Breaking Current630 / 1250 A
Rated Short-Circuit Making Current (peak)50 / 63 kA
Rated Short-Time Withstand Current20kA/4s, 25kA/4s
Rated Cable-Charging Breaking Current25 A
Rated Earth Fault Breaking Current48 A
Lightning Impulse Withstand (phase-phase/earth)125 kV
Lightning Impulse Withstand (across isolating distance)145 kV
Power Frequency Withstand 1min (phase-phase/earth)65 kV
Power Frequency Withstand 1min (across isolating distance)79 kV
Rain Test Withstand Voltage50 kV
Rated Working Pressure0.20 MPa
Low Pressure Interlock0.03-0.04 MPa
High Pressure Explosion Relief0.4-0.6 MPa
Annual Leak Rate≤0.5%
SF6 Water Content≤150 PPM
Circuit Resistance (per phase)≤150 μΩ
Contact Distance41±3 mm
Contact Overtravel22±2 mm
Opening Speed1.9±0.2 m/s
Closing Speed1.9±0.2 m/s
Contact Closing Bounce Time≤3 ms
Phase-to-Phase Distance250±3 mm
Three-Phase Synchronization≤3 ms
Closing Time<10 s
Opening Time<10 s
Energy Storage Motor Power40 W
Mechanical Life5,000 operations
Operation VoltageDC220V / DC24V / AC220V
Weight (Manual / Automatic)115 kg / 135 kg
Temperature Range-25°C to +40°C

应用领域

Urban distribution network sectionalizing (20kV)Tie switch applications for 20kV systemsRural distribution system control switchingRing network fault detection, isolation, and alarmDistribution automation with FTU

执行标准

IEC 62271-103GB/T 10963
12小时内回复ISO / CE / CCC 认证支持OEM定制

常见问题

SPG-24 Outdoor SF6 Load Break Switch (24kV)的额定电压是多少?
SPG-24 Outdoor SF6 Load Break Switch (24kV)的额定电压为24 kV。完整电气参数请参阅上方技术规格表。
SPG-24 Outdoor SF6 Load Break Switch (24kV)的交货周期是多久?
SPG-24 Outdoor SF6 Load Break Switch (24kV)的标准交货周期约为30天。大批量订单或定制配置可能需要额外生产时间。请联系我们的销售团队获取准确的交货时间。
SPG-24 Outdoor SF6 Load Break Switch (24kV)可以进行OEM定制吗?
可以,耐吉电气为SPG-24 Outdoor SF6 Load Break Switch (24kV)提供OEM和定制制造服务。我们可以根据项目需求调整规格、品牌和配置。最低起订量要求适用。
SPG-24 Outdoor SF6 Load Break Switch (24kV)符合哪些标准?
SPG-24 Outdoor SF6 Load Break Switch (24kV)按照IEC 62271-103, GB/T 10963标准设计和测试。所有产品出厂前均经过严格测试。

对SPG-24 Outdoor SF6 Load Break Switch (24kV)感兴趣?