The 27kV outdoor automatic recloser serves 24kV three-phase overhead distribution lines (50/60Hz), compliant with IEC 62271-111 and benchmarked against IEEE C37.60. Widely adopted in South America, North America, East/South Africa, Southeast Asia, and Oceania where 24kV grids prevail. Available in three-phase ganged single-mechanism or three-phase independent mechanism configurations — independent mechanism is preferred for export projects. Upgraded insulation distances and vacuum interrupter sizing compared to the 15.5kV model. 304/316 stainless steel enclosure with outdoor powder-coat protection.

Key Features

  • 27kV rated voltage, 630A rated current
  • Power-frequency withstand: 70kV; Lightning impulse: 150kV
  • 10,000 mechanical operations life
  • Closing time: ≤60ms; Opening time: ≤45ms
  • Partial discharge: ≤20pC at 1.1Ur/√3
  • Built-in CT: 600A/1A, accuracy class 0.5S
  • Three-phase ganged or independent mechanism
  • Upgraded insulation for 24kV systems
  • 304/316 stainless steel enclosure
  • IEC 62271-111 & IEEE C37.60 compliant

Technical Specifications

Rated Voltage27kV
Rated Current630A
Power-Frequency Withstand (Phase/Earth & Across Gap)70kV
Lightning Impulse Withstand (Peak)150kV
Mechanical Life10,000 operations
Contact Gap12±1mm
Closing Time≤60ms
Opening Time≤45ms
Partial Discharge≤20pC
Built-in CT Ratio600A/1A
CT Accuracy Class0.5S (5P10)
Operating Temperature-40°C to +45°C
Frequency50/60Hz
Enclosure Material304/316 Stainless Steel
StandardsIEC 62271-111, IEEE C37.60

Applications

24kV overhead distribution linesSouth America / Africa / Southeast Asia gridsDistribution automation (DA/FA)Fault isolation and auto-reclosing

Standards Compliance

IEC 62271-111IEEE C37.60
Reply within 12hISO / CE / CCC CertifiedOEM Available

Frequently Asked Questions

What is the rated voltage of the 27kV Outdoor Automatic Recloser?
The 27kV Outdoor Automatic Recloser has a rated voltage of 27kV. Please refer to the technical specifications table above for complete electrical ratings.
What is the lead time for 27kV Outdoor Automatic Recloser?
Standard lead time for the 27kV Outdoor Automatic Recloser is approximately 30 days. Larger quantities or custom configurations may require additional production time. Contact our sales team for a precise delivery schedule.
Can the 27kV Outdoor Automatic Recloser be customized for OEM projects?
Yes, NAIJI Electric offers OEM and custom manufacturing for the 27kV Outdoor Automatic Recloser. We can adjust specifications, branding, and configurations to meet project-specific requirements. Minimum order quantities apply.
What standards does the 27kV Outdoor Automatic Recloser comply with?
The 27kV Outdoor Automatic Recloser is designed and tested in accordance with IEC 62271-111, IEEE C37.60. All products undergo rigorous factory testing before shipment.

Interested in 27kV Outdoor Automatic Recloser?

Get factory-direct pricing, technical specifications, and custom configuration options.