MV Switchgear Specification: RFQ Checklist & Data Sheet (2026)

14 min read
NAIJI Electric Technical Team
medium voltage switchgear specificationMV switchgear RFQswitchgear data sheet
MV Switchgear Specification: RFQ Checklist & Data Sheet (2026)
Table of Contents

Quick Answer: The 12 Things Your RFQ Must State

A medium voltage switchgear specification produces comparable quotations only if it fixes twelve numbers: standard system, rated voltage, insulation level, frequency, busbar and feeder continuous current, short-time withstand current and duration, short-circuit breaking and making current, internal arc classification, LSC and partition class, construction type, protection and metering functions, and auxiliary voltages — plus site conditions. Everything else in a tender document is refinement. This guide walks through each one, explains what it costs when you get it wrong, and ends with a data sheet you can copy into your enquiry.

Engineer reviewing a medium voltage switchgear specification data sheet next to a metal-enclosed switchgear lineup

What a Vague Specification Actually Costs

We quote several hundred medium voltage enquiries a year for export projects. Roughly two thirds arrive incomplete, and the incompleteness is remarkably consistent. The five most common omissions, in order:

Missing itemHow oftenConsequence
Site altitude~70% of enquiriesWrong insulation class supplied; equipment fails site testing above 1,000 m
Internal arc classification~60%Untested enclosure quoted against a tested one; 15-25% price gap
LSC / partition class~55%LSC1 quoted against LSC2B PM; up to 30% price gap and no shutters
Short-circuit duration (1 s vs 3 s vs 4 s)~40%Busbar and earthing switch undersized; requote after clarification
Auxiliary and control voltage~35%Wrong coil and motor voltages; rework at site

None of these are exotic. They are all one line in a data sheet. The cost of leaving them out is measured in clarification rounds — each one adding 3-7 days to the schedule — and in bid spreads so wide that procurement cannot tell a cheap supplier from a non-compliant one.

Step 1: Fix the Standard System — and Do Not Mix

The first line of the specification should name the standard system and stop there.

AspectIEC routeANSI/IEEE route
Assembly standardIEC 62271-200 (1 kV to 52 kV)IEEE C37.20.2 (metal-clad), C37.20.3 (metal-enclosed interrupter)
Circuit breaker standardIEC 62271-100IEEE C37.04 / C37.06 / C37.09
Common clausesIEC 62271-1IEEE C37.100.1
Instrument transformersIEC 61869-2 (CT), 61869-3 (VT)IEEE C57.13
Construction classificationLSC1 / LSC2A / LSC2B + PM / PIMetal-clad vs metal-enclosed
Typical voltages3.6, 7.2, 12, 17.5, 24, 36, 40.5 kV4.76, 8.25, 15, 27, 38 kV
Short-circuit rating expressed askA rms for 1 s / 3 s / 4 skA rms symmetrical with a separate close-and-latch value

The two systems are not interchangeable at the detail level. An IEC 12 kV rating is not the same as an ANSI 15 kV class — the ANSI class carries a higher maximum design voltage and different BIL. Asking for "12 kV, metal-clad per C37.20.2, type tested to IEC 62271-200" is a contradiction that every serious bidder will query. Our IEC 62271 standards guide maps the series clause by clause, and the metal-clad vs metal-enclosed article reconciles the two naming systems.

Step 2: Electrical Ratings — From the System Study, Not the Last Project

Intelligent 12 kV medium voltage switchgear bay showing protection relay, metering and busbar compartment

Every rating below has a direct cost consequence, so each should come from a short-circuit and load flow study rather than being copied forward.

RatingSymbolCommon valuesCost sensitivity
Rated voltageUr12 / 24 / 40.5 kVHigh — drives clearances, bushings, bay width
Lightning impulse withstand (BIL)Up75 kV at 12 kV; 125 kV at 24 kV; 185 kV at 40.5 kVHigh — fixed by voltage class and altitude
Power-frequency withstand, 1 minUd42 kV at 12 kV; 50 kV at 24 kV; 95 kV at 40.5 kVIncluded with class
Rated frequencyfr50 or 60 HzLow, but must be stated for CT and relay sizing
Busbar continuous currentIr630 / 1,250 / 1,600 / 2,500 / 3,150 AMedium — copper cross-section
Feeder continuous currentIr630 / 1,250 A typicalMedium
Short-time withstand current + durationIk / tk20 / 25 / 31.5 / 40 kA for 1 s, 3 s or 4 sHigh — 25 to 31.5 kA moves a bay 10-15%
Peak withstand currentIp2.5 × Ik at 50 Hz; 2.6 × at 60 HzDerived, but state it
Short-circuit breaking currentIscMatches IkHigh
Short-circuit making current= IpApplies to breaker and earthing switch
Operating sequenceO-0.3s-CO-180s-COLow, but affects auto-reclose duty

The duration trap. "31.5 kA" alone is incomplete. 31.5 kA for 1 s and 31.5 kA for 3 s are different products: the thermal energy the busbar must absorb scales with I²t, so tripling the duration triples the energy and forces larger bars and stronger supports. Utility specifications commonly ask for 3 s or 4 s; industrial specifications usually accept 1 s. Say which. Our short-circuit rating calculation guide shows how to derive these from the utility fault level, and circuit breaker ratings explained covers what each nameplate figure governs.

Step 3: Construction and Classification

This is where the same words describe very different hardware, and where bid spreads open up widest.

  • Loss of service continuity: LSC1 (others must be de-energized), LSC2A (busbar stays live), LSC2B (busbar and adjacent cable compartments stay live). Utility and critical industrial work almost always needs LSC2B.
  • Partition class: PM (partial metallic, earthed metal partitions and shutters) or PI (partial insulating). Specify PM where you want ANSI metal-clad equivalence.
  • Internal arc: the full Annex AA code, e.g. IAC AFLR 31.5 kA 1 s. A = authorized personnel access; F, L, R = front, lateral, rear protected.
  • Construction: drawout (withdrawable truck with service / test / isolated positions) or fixed-mounted. Fixed is roughly 10-20% cheaper per bay but requires a full bay outage for breaker maintenance.
  • Degree of protection: IP4X enclosure and IP2X between compartments is the usual indoor requirement; IP54 for dusty or humid plant rooms.
  • Cable entry: bottom or top, front or rear access, number and size of cables per phase per feeder. State it — it fixes the bay depth.

The single sentence that resolves most ambiguity: "Switchgear shall be metal-enclosed to IEC 62271-200, classified LSC2B, partition class PM, internal arc classified IAC AFLR 31.5 kA 1 s, with withdrawable vacuum circuit breakers." That one line removes three of the five commonest omissions. NAIJI's ASN3-12, ASN2-24 and ASN1-40.5 are built to that construction; the compact ASN550 and the GSN3-12 gas-insulated design cover space-constrained rooms.

Have a draft specification you want checked before it goes out to tender? Send it over — our engineers will flag the gaps that cause requotes, at no cost. Contact NAIJI Electric.

Step 4: Protection, Metering and Control

Protection is the largest single variable cost inside an MV bay, at 20-35% of bay price, so specify function rather than brand unless the brand is genuinely mandated by an existing SCADA estate.

ApplicationANSI device functionsNotes
Incomer50/51, 50N/51N, 27, 59, 81, 32, 25 (if paralleling)Add 87B for busbar differential on critical schemes
Bus tie50/51, 50N/51N, 25Synchro-check where closing onto a live bus
Transformer feeder50/51, 50N/51N, 87T, 49, 63/26 (trip inputs)87T needs matched CT ratios both sides
Motor feeder49, 50, 51, 46, 37, 66, 51LRThermal model settings from motor data sheet
Capacitor bank50/51, 59, 60, 51NUnbalance protection essential
Line feeder50/51, 50N/51N, 79, 67 where directional79 auto-reclose only on overhead circuits

Then state the supporting items that are routinely forgotten:

  • CT ratios, class and burden — e.g. 600/5 A, 5P20, 15 VA for protection; 0.5S for metering. Separate cores for protection and metering.
  • VT ratios and class — e.g. 11,000/√3 : 110/√3 V, class 0.5 / 3P, with primary fuses.
  • Auxiliary voltages — closing coil, tripping coil, spring charging motor, space heaters and lighting. DC 110 V and DC 220 V are the usual control voltages; AC 230 V for heaters. State each separately.
  • Communication — IEC 61850 (state edition and whether GOOSE is required), Modbus RTU/TCP or DNP3. IEC 61850 with GOOSE typically adds cost and factory test time; ask for it only if the SCADA will use it.
  • Trip circuit supervision, lockout relay (86), and local/remote selector — cheap items that cause site rework when unstated.

Our MV protection relay guide and relay type selection guide cover function selection in depth.

Step 5: Site Conditions — the Altitude Clause Everyone Forgets

IEC 62271-1 defines normal service conditions as altitude not exceeding 1,000 m, ambient air temperature not exceeding +40 °C with a 24-hour average not exceeding +35 °C, and a minimum of −5 °C, −15 °C or −25 °C depending on the class.

Above 1,000 m the insulation must be corrected by the factor:

Ka = e^(m(H − 1000)/8150)

where H is altitude in metres and m = 1 for power-frequency and lightning impulse withstand on this class of equipment. Worked examples:

Site altitudeCorrection factor KaRequired withstand upliftPractical solution for a 12 kV system
1,000 m1.00NoneStandard 12 kV equipment
1,500 m1.06+6%Standard 12 kV, verify with maker
2,000 m1.13+13%Uprated 12 kV or 17.5 kV class
2,500 m1.20+20%24 kV class equipment for a 12 kV system
3,500 m1.36+36%24 kV class plus continuous current derating

Continuous current also derates with altitude because thinner air removes less heat — typically around 0.5% per 100 m above 1,000 m. Projects in the Andes, the Ethiopian highlands, Central Asia and western China hit this constantly, and it is the single most expensive omission we see because it changes the equipment class after the price is agreed.

Other site data to state: ambient maximum and minimum, relative humidity, seismic zone or required spectrum, pollution level for outdoor components, and whether the room is air-conditioned. Also give the physical constraints — door width, corridor turns, floor loading, ceiling height and arc venting route — before drawings are made, not after. See our installation and commissioning guide.

Step 6: Tests — Separate Type, Routine, FAT and SAT

CategoryPerformed onWhat to require in the RFQ
Type testsA representative design, onceCertificates submitted with the bid: dielectric, short-time withstand, breaking capacity, temperature rise, internal arc, mechanical endurance, IP, EMC
Routine testsEvery unit, before dispatchPower-frequency withstand on main circuit, dielectric on auxiliary circuits, mechanical operation, wiring and function check, protective circuit continuity, measurement of main circuit resistance
Factory acceptance testYour actual assemblyWitnessed or unwitnessed; state the notice period, the test schedule, and whether relay injection testing is included
Site acceptance testAfter installationContact resistance, insulation resistance, vacuum integrity, interlock proving, relay injection, primary injection where feasible

Requiring type test certificates with the bid rather than after award is the highest-leverage line in any switchgear RFQ. It removes suppliers who intend to test after they win, and it is free to ask. Detail in our switchgear testing standards guide and maintenance and testing guide.

Step 7: Documentation, Spares and Packing

  • General arrangement, single-line diagram, schematic and wiring diagrams, terminal plans, foundation and cable entry drawings — state the approval round count and turnaround days
  • Bill of materials with make and model of every bought-in component
  • Type and routine test reports, factory acceptance test report
  • Operation and maintenance manual, in the project language
  • Nameplate data and arc-flash labels with the incident energy assessment basis
  • Two-year commissioning spares and five-year operational spares, priced separately
  • Packing: seaworthy plywood cases, desiccant, moisture indicator, shock indicator on the breaker cases, container loading plan and weights
  • Warranty period and response commitment; whether supervision of erection and commissioning is included

Copy-Paste RFQ Data Sheet Template

Paste this into your enquiry and fill in the right column. Bids answering all of it will be genuinely comparable.

ItemYour value
Project name / location / site altitude (m)
Standard system (IEC 62271-200 / ANSI C37.20.2 / C37.20.3)
Rated voltage Ur (kV) and system nominal voltage (kV)
Rated insulation level: BIL (kV peak) / 1 min power frequency (kV rms)
Rated frequency (Hz)
Busbar rated continuous current (A)
Feeder rated continuous current (A), per bay
Rated short-time withstand current (kA) and duration (1 s / 3 s / 4 s)
Rated peak / making current (kA peak)
Neutral earthing method (solid / resistance / resonant / isolated)
LSC class and partition class (e.g. LSC2B PM)
Internal arc classification (e.g. IAC AFLR 31.5 kA 1 s)
Construction (drawout / fixed) and IP degree
Bay schedule: quantity and function of each bay (incomer / tie / feeder / VT / metering)
Protection functions per bay (ANSI device numbers)
Relay brand preference or "compliant equivalent acceptable"
CT ratios, class, burden, cores per bay
VT ratios, class, connection, fusing
Control voltage (DC V) / spring charge motor / heater supply (AC V)
Communication protocol (IEC 61850 / Modbus / DNP3) and SCADA interface
Cable entry: top or bottom, front or rear, cable size and quantity per phase
Ambient temperature range, humidity, seismic requirement
Room constraints: door width, corridor, floor loading, ceiling height, venting route
Paint finish and RAL colour
Test requirements: type certificates with bid? FAT witnessed? SAT scope?
Documentation, spares, packing, warranty, Incoterm and destination port
Required delivery date and drawing approval turnaround

Ten Specification Mistakes That Trigger a Requote

  1. Stating kA without the duration
  2. Saying "arc resistant" instead of an IAC code with accessibility letters and time
  3. Omitting site altitude on a highland project
  4. Mixing IEC and ANSI clauses in one document without a priority statement
  5. Specifying a busbar current lower than the sum of the feeders it must carry
  6. Naming a relay brand without allowing a compliant equivalent, then comparing on price
  7. Leaving CT burden and class unstated, so protection cores are undersized
  8. Forgetting the control voltage, which determines coil, motor and relay power supply
  9. Not stating cable size and quantity, which fixes bay depth and termination arrangement
  10. Approving drawings late — the most common cause of a missed delivery date, and one that sits on the buyer's side

If you are also evaluating who to send the RFQ to, our switchgear manufacturer selection guide and China sourcing guide cover audit, certification and payment terms.

What Compliant Bids Should Look Like

Bay typeRatingIndicative FOB ChinaLead time from approved drawings
12 kV feeder, VCB, LSC2B PM, IAC AFLR 31.5 kA 1 s12 kV / 630-1,250 A / 31.5 kA$2,800 - $6,50025 - 40 days
12 kV incomer with metering12 kV / 1,250-2,500 A$4,500 - $9,00025 - 40 days
24 kV feeder, VCB24 kV / 630-1,250 A / 25 kA$5,000 - $12,00030 - 45 days
40.5 kV feeder, VCB40.5 kV / 1,250-1,600 A / 31.5 kA$8,000 - $18,00035 - 50 days
12 kV gas-insulated feeder12 kV / 630 A / 25 kA$6,000 - $14,00035 - 50 days

Prices are indicative, confirmed against your data sheet, and MOQ is flexible — we supply single bays for retrofit and extension work as well as complete lineups. If the lineup is being sized as well as specified, our lineup design and configuration guide covers bay count and bus arrangement, and our LV vs MV switchgear comparison covers whether you need the MV lineup at all.

Bottom Line

A medium voltage switchgear specification is not a technical essay — it is a set of numbers that make bids comparable. Fix the standard system, the ratings with their durations, the classification codes, the protection functions, the auxiliary voltages and the site conditions, and the price spread between compliant suppliers usually falls under 15%. Leave them open and you are not comparing suppliers; you are comparing assumptions.

Send Us Your Specification for a Quotation →

Related guides: IEC 62271 Standards Guide | Metal-Enclosed Switchgear Guide | Short-Circuit Rating Calculation | Choosing a Switchgear Manufacturer | LV vs MV Switchgear | MV Protection Relay Guide

Frequently Asked Questions

What must a medium voltage switchgear specification include?
At minimum, twelve items: standard system (IEC or ANSI), rated voltage and insulation level (BIL and power-frequency withstand), rated frequency, rated continuous current of busbar and each feeder, rated short-time withstand current and duration, rated short-circuit breaking and making current, internal arc classification with duration, loss of service continuity and partition class, construction type (drawout or fixed), protection and metering functions, auxiliary and control voltages, and site conditions including altitude, ambient temperature and humidity. Omit any one of these and quotations become non-comparable.
Should I specify to IEC or ANSI standards?
Choose the system that matches the rest of your installation and your local grid code, then apply it consistently. IEC 62271-200 governs metal-enclosed switchgear from 1 kV to 52 kV and is the norm in Europe, the Middle East, Africa, South Asia, Southeast Asia and China. ANSI/IEEE C37.20.2 for metal-clad and C37.20.3 for metal-enclosed interrupter switchgear govern in North America and parts of Latin America and the Gulf. Mixing them — for example asking for an ANSI metal-clad definition with IEC voltage ratings and IEC test certificates — produces quotations that cannot be compared and usually a requote after technical clarification.
How do I state internal arc requirements correctly?
Write the full IEC 62271-200 Annex AA code, not the words "arc resistant". The format is IAC, then accessibility letters, then current and duration: for example IAC AFLR 31.5 kA 1 s. A means access restricted to authorized personnel, F means the front is protected, L the lateral sides, R the rear. Match the kA figure to your prospective short-circuit current and the duration to your protection clearing time plus margin. An enclosure with no stated classification has no tested behaviour under internal arc, whatever the brochure implies.
What altitude derating applies to medium voltage switchgear?
IEC 62271-1 requires correction of the insulation level above 1,000 m. The correction factor is Ka = e^(m(H−1000)/8150), where H is altitude in metres and m is 1 for power-frequency and lightning impulse withstand on this equipment class. In practice, insulation withstand falls roughly 1.0-1.25% per 100 m above 1,000 m, so a site at 2,500 m needs switchgear rated approximately 20% above the nominal system requirement — typically achieved by supplying 24 kV rated equipment for a 12 kV system. Continuous current also derates because air cools less effectively. State the site altitude in the RFQ; this is one of the most frequently omitted items and it changes the equipment class.
What tests should I require in the RFQ?
Distinguish three categories clearly. Type tests are done once on a representative design — dielectric, short-time withstand, breaking capacity, temperature rise, internal arc, mechanical operation, IP rating — and you should require the certificates with the bid, not after the order. Routine tests are done on every unit before shipment: power-frequency withstand, auxiliary circuit dielectric, mechanical operation, protective circuit continuity, wiring check. Factory acceptance testing is your witnessed inspection of the actual assembly, which you should schedule and define in the RFQ. Site acceptance testing after installation typically covers contact resistance, insulation resistance, vacuum interrupter integrity and relay injection.
How long does medium voltage switchgear take to manufacture?
Standard lead time from NAIJI is 25-40 days for 12 kV metal-enclosed bays, 30-45 days for 24 kV and 35-50 days for 40.5 kV or gas-insulated designs, measured from approved drawings rather than from order date. Drawing approval typically adds 7-15 days depending on how many review rounds the client needs. Long-lead items that can extend this are specific European protection relays, non-standard current transformer ratios and special paint or seismic requirements. A complete and unambiguous RFQ shortens drawing approval more than anything else in the schedule.
Why do switchgear quotations from different suppliers vary so much?
Almost always because the specification left something open. The five biggest price levers are short-circuit rating (25 kA versus 31.5 kA can move a bay 10-15%), internal arc classification and duration, LSC and partition class, protection relay brand (20-35% of bay cost), and busbar rated current. A quotation that omits any of these is not necessarily cheating — it is answering a different question. Lock those five in the RFQ and the spread between compliant bids usually narrows to under 15%.

Related Articles

14 min read

MV Switchgear for BESS: Duty Classes, Inverter Fault Current & Spec Guide

A BESS breaker sees 700-1,500 operations a year against an M1 rating of 2,000. And a PCS contributes only 1.1-1.5 pu into a fault, so conventional overcurrent goes blind. Duty-class maths, protection tables and copy-paste spec wording from an MV switchgear manufacturer. 30-60 day lead time. Get a quote →

Read Article
22 min read

IEC 62271 Standard Explained: Type Tests, IAC Arc Ratings & Switchgear Compliance Guide [2026]

IEC 62271-100/-200/-203 decoded: type test requirements, IAC arc classification (AFL/AFLR), LSC categories, BIL ratings. 7 sub-standards in one engineer checklist. ISO-certified manufacturer — get quote →

Read Article
14 min read

Metal-Enclosed Switchgear: Types, Standards & Selection Guide (IEC 62271-200)

What metal-enclosed switchgear is, how IEC 62271-200 loss of service continuity and partition classes work, how ANSI C37.20.3 metal-enclosed interrupter switchgear differs from C37.20.2 metal-clad, plus ratings tables, pricing and a specification checklist from a Chinese switchgear manufacturer.

Read Article
15 min read

Switchgear Short-Circuit Rating: How to Calculate & Specify kA Ratings (IEC & ANSI)

Practical guide to understanding and specifying switchgear short-circuit ratings. Covers symmetrical and asymmetrical fault current, making capacity, short-time withstand current, IEC 62271-1 and ANSI C37.06 rating systems, and how to match switchgear ratings to system fault levels.

Read Article
11 min read

How to Choose a Medium Voltage Switchgear Manufacturer: 8 Key Criteria (2026 Guide)

A practical guide covering the 8 critical criteria for selecting a reliable medium voltage switchgear manufacturer — certifications, production capacity, technical capability, product range, customization, lead time, after-sales service, and pricing. Includes a scoring checklist for supplier evaluation.

Read Article

Need Help Selecting Switchgear?

Our engineering team can recommend the right products for your project. Get factory-direct pricing from an ISO/CE certified manufacturer.